73% saved

Other Lighting Upgrade in Newark, NJ

Newark, NJ2026-07-30

Commercial LED lighting upgrade completed by VK Light Solutions.

Other
Facility

0 sq ft

Fixtures

100 installed

Energy Saved

73%

Yearly Savings

$15,444

Duration

Challenge

The facility in Newark, New Jersey was operating 100 legacy 450-watt HiBay fixtures, drawing a combined 45.0 kW across a 10-hour-per-day, five-day-per-week schedule. That operating profile meant the aging high-intensity fixtures were consuming significant electricity year-round with no controls in place to reduce demand during low-activity periods. The combination of high per-fixture wattage and consistent daily runtime made the lighting system one of the facility's most consequential energy costs.

Solution

VK Light Solutions replaced all 100 existing HiBay fixtures with DLC-listed LED HiBay fixtures rated at 120 watts each, reducing the total connected load from 45.0 kW to 12.0 kW. The retrofit was a direct one-for-one fixture replacement, preserving the existing layout while dramatically lowering energy draw at every luminaire position. The new LED HiBay fixtures were selected to deliver the light output required for the facility's operating environment at a fraction of the prior wattage.

Energy Savings

The retrofit eliminated 85,800 kWh of electricity consumption per year, representing a 73% reduction in lighting energy use. At the facility's rate of $0.180 per kWh, that reduction translates to $15,444 in annual dollar savings. The project also avoids 72,930 pounds of CO2 emissions each year as a direct result of the lower energy demand.

Results

The facility now operates with a lighting load of 12.0 kW instead of 45.0 kW, producing a measurable and recurring reduction in utility costs of $15,444 every year. The transition to LED HiBay fixtures also reduces the frequency of lamp replacements and associated maintenance labor compared to the previous high-intensity fixtures. With no rebate program available for this project, the full savings return flows directly from the energy reduction alone, making the performance of the fixture selection the sole driver of the financial outcome.

Project Details

Location
Newark, NJ
Completed
2026
Facility Size
0 sq ft
Fixtures Installed
100 fixtures
Fixture Type
LED HiBay

Energy Savings

Before (per fixture)450W
After (per fixture)120W
Energy Saved73%

Want similar results for your facility?

Get Free QuoteContact Us

Lighting Upgrade Details

HiBay Upgrade

βˆ’73% watts

Before

450W HiBay

After

120W LED HiBay

Quantity
100 fixtures

Installed Fixtures

  • LED HiBay
  • HiBay

Installed Controls & Smart Systems

  • Occupancy Sensor
  • Motion Sensor

How the Savings Math Works

Same formula we use on every commercial energy audit, shown openly.

Before

100 fixtures Γ— 450W Γ— 10h Γ— 5d Γ— 52w Γ· 1,000
= 117,000 kWh / year
Γ— $0.18/kWh
= $21,060 / year

After

100 fixtures Γ— 120W Γ— 10h Γ— 5d Γ— 52w Γ· 1,000
= 31,200 kWh / year
Γ— $0.18/kWh
= $5,616 / year

Annual Savings

85,800
kWh saved / year
$15,444
$ saved / year at $0.18/kWh
73%
per-fixture wattage reduction