Skip to main content
Office LED Lighting Upgrade in Amboy, NJ — Amboy, NJ
Office
63% saved

Office LED Lighting Upgrade in Amboy, NJ

Amboy, NJ2026-07-233 days

Commercial LED lighting upgrade completed by VK Light Solutions.

Office
Instalações

7,100 sq ft

Luminárias

40 instaladas

Energia economizada

63%

Economia anual

$880

Duração

3 days

Desafio

This 7,100 square foot office in Amboy, New Jersey was running 40 two-by-two fluorescent troffers drawing a combined 3.0 kilowatts across a 10-hour, five-day-per-week schedule. The aging fluorescent fixtures delivered inconsistent light levels and drove up electricity costs at a rate of $0.18 per kWh. The facility owner needed a durable, cost-effective solution that would meaningfully reduce the lighting load without disrupting the occupied workspace.

Solução

VK Light Solutions replaced all 40 fluorescent troffers with DLC-listed 2x2 LED panels rated at 28 watts each, reducing the total connected load from 3.0 kilowatts down to 1.1 kilowatts. Occupancy sensors were installed throughout the office to deliver an additional 30% runtime reduction on the new LED fixtures during unoccupied periods. Together, the fixture swap and sensor controls were engineered as a single integrated retrofit to maximize verified energy savings.

Economia de energia

The retrofit eliminates 5,762 kWh of electricity consumption per year, representing a 74% reduction in lighting energy use for the facility. At the local rate of $0.18 per kWh, that reduction translates to $1,037 in annual utility savings. The project also avoids 4,897 pounds of CO2 emissions each year.

Resultados

The Amboy office now operates with a lighting system that consumes roughly one-quarter of the electricity the prior fluorescent troffers required, lowering the facility's annual utility costs by over a thousand dollars. LED panel technology reduces lamp-replacement frequency compared to fluorescent sources, cutting ongoing maintenance demands for the property. The addition of occupancy sensors ensures the efficiency gains extend beyond fixture wattage alone, automatically reducing runtime whenever spaces are unoccupied.

Serviços realizados

  • office-lighting

Detalhes do projeto

Localização
Amboy, NJ
Concluído
2026
Tamanho das instalações
7,100 sq ft
Luminárias instaladas
40 luminárias
Tipo de luminária
2x2 LED Panel

Economia de energia

Antes (por luminária)75W
Depois (por luminária)28W
Energia economizada63%

Quer resultados parecidos para as suas instalações?

Orçamento grátisFale conosco

Detalhes da modernização da iluminação

Atualização de 2x4 Panel

−-179% watts

Antes

90W 2x4 Fluorescent Troffer

Depois

251W 2x4 LED Panel

Atualização de 2x2 Panel

−60% watts

Antes

60W 2x2 Fluorescent Troffer

Depois

24W 2x2 LED Panel

Quantidade
20 luminárias

Atualização de 4ft Strip

−64% watts

Antes

90W 4ft Fluorescent Strip

Depois

32W 4ft LED Strip

Quantidade
20 luminárias

Luminárias instaladas

  • 2x4 LED Panel
  • 2x2 LED Panel
  • 4ft LED Strip
  • 4ft Strip
  • LED Panel 2x4
  • LED Panel 2x2

Controles e sistemas inteligentes instalados

  • Occupancy Sensor
  • Motion Sensor
  • Smart Switch
  • Smart Dimmer
  • Wireless Control Module
  • Smart Hub Control
  • Smart Lighting Control System

Como funciona o cálculo da economia

A mesma fórmula que usamos em cada auditoria energética comercial, mostrada abertamente.

Antes

40 luminárias × 75W × 10h × 5d × 52sem ÷ 1.000
= 7,800 kWh / ano
× $0.18/kWh
= $1,404 / ano

Depois

40 luminárias × 28W × 10h × 5d × 52sem ÷ 1.000
= 2,912 kWh / ano
× $0.18/kWh
= $524 / ano

Economia anual

4,888
kWh economizados / ano
$880
$ economizados / ano a $0.18/kWh
63%
redução de potência por luminária

Fotos do projeto

Want Similar Results at Your Facility?

Every project starts with a free on-site audit and a written photometric design. We file rebates, manage install, and verify the savings against the proposal.